Category: To Confirm
Supply for Compact or Fieldbus CPU, X2X Link network and internal I/O power supply Electrical isolation of supply and CPU / X2X Link power supply Redundancy of CPU / X2X Link supply possible by operating multiple supply modules simultaneously RS232 configurable as an online interface CAN bus The power supply module is used together with an X20 Compact or Fieldbus CPU.
It is equipped with a supply for the Compact or Fieldbus CPU, X2X Link network and internal I/O power supply.
Technical Specifications
Short description
- Power supply module = 24 VDC power supply module for Compact or Fieldbus CPU, X2X Link power supply and I/O
- Interfaces = 1x RS232, 1x CAN bus
General information
- Diagnostics
- Module run/error = Yes, using LED status indicator and software
- CAN bus data transfer = Yes, using LED status indicator
- RS232 data transfer = Yes, using LED status indicator
- Overload = Yes, using LED status indicator and software
- Power consumption
- Internal I/O = 0.6 W
- Certifications
- CE = Yes
- UKCA = Yes
- ATEX = Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
- UL = cULus E115267 Industrial control equipment
- HazLoc = cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
- DNV = Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
- CCS = Yes
- LR = ENV1
- KR = Yes
- ABS = Yes
- BV = EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
- KC = Yes
- B&R ID code = 0x2018
- Status indicators = Overload, operating state, module status, RS232, CAN bus
- Power consumption for X2X Link power supply = 1.42 W
- Additional power dissipation caused by actuators (resistive) [W] = -
CPU / X2X Link power supply input
- Input voltage = 24 VDC -15% / +20%
- Input current = Max. 0.7 A
- Fuse = Integrated, cannot be replaced
- Reverse polarity protection = Yes
CPU / X2X Link power supply output
- Nominal output power = 7 W
- Parallel connection = Yes
- Redundant operation = Yes
- Overload characteristics = Short-circuit proof, temporary overload
Input I/O power supply
- Input voltage = 24 VDC -15% / +20%
- Fuse = Required line fuse: Max. 10 A, slow-blow
- Reverse polarity protection = No
Output I/O power supply
- Nominal output voltage = 24 VDC
- Behavior on short circuit = Required line fuse
- Permissible contact load = 10 A
Interfaces
- Interface IF1
- Signal = RS232
- Variant = Connection via 12-pin terminal block X20TB12
- Transfer rate = Max. 115.2 kbit/s
- Interface IF3
- Signal = CAN bus
- Transfer rate = Max. 1 Mbit/s
Electrical properties
- Electrical isolation = CPU/X2X Link supply isolated from CPU/X2X Link power supply I/O supply not isolated from I/O power supply
Operating conditions
- Mounting orientation
- Horizontal = Yes
- Vertical = Yes
- Installation elevation above sea level
- 0 to 2000 m = No limitation
- >2000 m = Reduction of ambient temperature by 0.5°C per 100 m
- Degree of protection per EN 60529 = IP20
Ambient conditions
- Temperature
- Operation
- Horizontal mounting orientation = -25 to 60°C
- Vertical mounting orientation = -25 to 50°C
- Derating = See section "Derating".
- Storage = -40 to 85°C
- Transport = -40 to 85°C
- Relative humidity
- Operation = 5 to 95%, non-condensing
- Storage = 5 to 95%, non-condensing
- Transport = 5 to 95%, non-condensing
Mechanical properties
- Note = Order 1x terminal block X20TB12 separately. Order 1x Compact CPU base X20BB22 or X20BB27 separately Order 1x Fieldbus CPU base X20BB3x/4x separately
- Pitch = 12.5 +0.2 mm