KL2622 | Bus Terminal, 2-channel relay output, 230 V AC, 30 V DC, 5 A, without power contacts
The KL2622 output terminal has two relays, each with a single contact, and can be used to switch devices requiring mains power and operating at up to 230...
Technical Specifications
KL2622 Number of outputs 2 x make contacts Nominal voltage 230 V AC/30 V DC Load type ohmic, inductive, lamp load Max. output current 5 A per channel Switching current 5 A AC/DC (ohmic)/2 A AC/DC (inductive) Ohmic switching current 5 A AC/DC Inductive switching current 2 A AC/DC Minimum permitted load 10 mA at 5 V DC Lamp test, electronic ballast max. 5 A starting current (4 x 58 W) Electrical isolation 500 V (K-bus/field potential) Current consumption power contacts – Current consumption K-bus typ. 85 mA Bit width in the process image 2 outputs Operating cycles mech. (min.) 2 x 10 7 Operating cycles electr. (min.) 1 x 10 5 (5 A/30 V DC) Configuration no address or configuration setting Special features potential-free contacts Weight approx. 80 g Operating temperature -25…+60°C Storage temperature -40…+85°C Relative humidity 95%, no condensation Vibration/shock resistance conforms to EN
Availability: regular delivery